The round duct diameter for an airflow and your design friction rate, the velocity it gives against the supply or return limit, and the rectangle with the same friction — drawn to scale. One section of sheet-metal duct, not a Manual D design.
1Round duct size
Example: 400 cfm at 0.073 in./100 ft (0.31 in. of static pressure over 424 ft, Energy Vanguard’s worked example). Change any number.
Suggested supply duct Example
11″round, whole inch
Suggested 11 inch round duct at 606 feet per minute; exact 10.34 inches.
606 fpm in this ductexact 10.34 in at 0.073 in./100 ft
Sections and velocityDrawn to scale: sections in inches, velocity in fpm
Duct section
Exact diameter, 10.34″
Velocity limit (as reported)
Velocity
606fpm, limit 900
Friction
0.054in./100 ft
One size up
12 in509 fpm
D at FR 0.073 = 10.34 inD at 900 fpm = 9.03 innext whole inch above both = 11 in
Already showing the example.
Read with the result
One section of galvanized sheet-metal round duct at standard air (70 °F, sea level). Not flex duct, fittings or a Manual D design.Roughness 0.0003 ft (ASHRAE); air 0.075 lb/ft³ (AMCA).
How the math works
The calculator finds the diameter at which the duct loses exactly your friction rate, using the Darcy equation with the Altshul–Tsal friction factor that ASHRAE’s Duct Design chapter gives. Then it checks the velocity and rounds up to a whole inch.
VelocityV = cfm ÷ (π/4 × (D/12)²) fpm
Reynolds numberRe = (V/60) × (D/12) ÷ 0.00015783Kinematic viscosity of standard air at 70 °F, our arithmetic from NASA’s Sutherland formula and AMCA’s density.
Friction factorf′ = 0.11 × (12 × 0.0003 ÷ D + 68 ÷ Re)^0.25; below 0.018, f = 0.85 f′ + 0.0028Altshul–Tsal, with ASHRAE’s “average” roughness for galvanized duct (0.0003 ft).
Friction rateFR = (12 f × 100 ÷ D) × 0.075 × (V ÷ 1097)²Darcy equation in inch-pound units, in. w.c. per 100 ft. The calculator solves it for D by bisection.
Velocity checkD for the limit = 12 × √(4 × cfm ÷ (π × limit))Limits 900 fpm supply and 700 fpm return: Manual D Table N3-1 as reported by Energy Vanguard, not yet confirmed in Manual D itself.
Suggested sizenext whole inch at or above the larger of the two diametersOne size up is shown too. Check which sizes your supplier stocks; we print no list of standard sizes.
RectangleDe = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25Huebscher equation: same friction per 100 ft at the same airflow. The rectangle has more area, so its air moves slower.
Worked examples
400 cfm at 0.073, supplyexact 10.34 in at 686 fpm → 11 in at 606 fpm, FR 0.054
1,200 cfm at 0.10, supply14.59 in would run 1,034 fpm; for 900 fpm D = 15.64 in → 16 in at 859 fpm
12 in round, 8 in sideother side = 15.47 in (check: De(8, 15.47) = 12.00 in)
Values the calculator uses
Duct roughness
0.0003 ft, galvanized sheet metalASHRAE (ashrae.org eSociety, April 2019): "average" absolute roughness of galvanized steel ducts
Air density
0.075 lb/ft³, standard airAMCA International, "The Fundamentals of Airflow" (2020): standard air, 70 °F, sea level
Kinematic viscosity
1.5783 × 10⁻⁴ ft²/s at 70 °FSite arithmetic: NASA Glenn Sutherland viscosity at 70 °F ÷ AMCA standard-air density 0.075 lb/ft³
Velocity limits
Supply 900 fpm · return 700 fpm As reportedEnergy Vanguard, "Duct Design 5 — Sizing the Ducts" (2017), citing ACCA Manual D Table N3-1. Reported by Energy Vanguard as Manual D Table N3-1 values; not yet confirmed in Manual D itself.
Low friction warning
Below 0.06 in. w.c. per 100 ftICC, "An Overview on ACCA’s Residential HVAC System Design Process" (2018 slides): the acceptable-FR wedge's edge is labelled 0.06
Before you use the number
Galvanized round duct only. Flex duct is rougher, and compressing it can raise the pressure drop four times or more (LBNL). There is no flex mode, because a single number would mislead.
The friction rate is an input, not a guess. Manual D derives it from the static pressure available for the ducts and the total effective length. Assuming 0.10 undersizes ducts (Energy Vanguard; ICC/ACCA).
Velocity matters too. If the size that meets the friction rate moves air faster than the limit, go larger. The limits shown are reported values, not code requirements.
One section, not a system. Fittings, equivalent lengths, registers, balancing dampers and the blower table are not included. Residential codes reference Manual D for the design.
Standard air. 70 °F at sea level. Altitude and temperature change the result; the calculator does not correct for them. A paper duct calculator may read a few percent differently.
Often yes: since July 27, 2026, EPA lets you install R-410A AC and heat pump equipment made in or imported to the U.S. before 2025. Dates, NY, quoting.
Length
7 min
Updated
Tools for the job
Tool listHVAC + Cross-trade4 itemsSpecs read
As an Amazon Associate, Trade Price Book earns from qualifying purchases. Amazon links are marked “(paid link)”; prices aren’t shown here.
ItemMaker, model and specsMaker · modelDescriptionFrom the maker’s pageAmazon
1
Digital manifolds and probesFieldpieceJL3KH6
JL3KH6 Job Link System Probes Wireless Charge & Air Test Kit
Six probes in a padded case: 2 pressure probes, 2 pipe-clamp temperature probes and 2 psychrometers.