Type any two of volts, amps, ohms and watts and get the other two — or convert kW and kVA to amps for single- and three-phase loads with a power factor. Drawn to scale. It converts quantities; it does not size wire or breakers.
1Volts, amps, ohms, watts
Example: a 12 Ω heating element on 120 V. Type any two values.
Volts, amps, ohms and wattsDrawn to scale on both axes
Volts given
120 Vvoltage
Amps worked out
10 Acurrent
Ohms given
12 Ωresistance
Watts worked out
1,200 Wpower
I = 120 V ÷ 12 Ω = 10 AP = 120² ÷ 12 = 1,200 W
Already showing the example.
Read with the result
DC, or AC in a purely resistive load with rms values. For motors and other inductive loads use AC power.HyperPhysics, “Electric Power”.
Calculated current is not a wire or breaker size. Conductors and overcurrent devices follow the electrical code and the equipment’s listing and instructions.
How the math works
Ohm’s law and the power relations, as HyperPhysics and NIST state them, plus the Department of Energy’s three-phase power equation. Every result keeps full precision; only the display is rounded.
CurrentI = V ÷ RRearranged: V = I × R and R = V ÷ I.
PowerP = V × I = I² × R = V² ÷ RHolds for DC, and for AC in a resistor with rms values.
Single-phase ACkW = V × I × PF ÷ 1,000 · I = kW × 1,000 ÷ (V × PF)
Three-phase ACkW = √3 × V × I × PF ÷ 1,000DOE Equation 1: V is the line-to-line voltage, I the line current, for a balanced load. √3 is computed (1.7320508…), so results can differ from a 1.732 hand calculation in the fifth figure.
kVA to ampsI = kVA × 1,000 ÷ V (single) · ÷ (√3 × V) (three)Apparent power ignores the power factor.
kW and kVAkW = kVA × PFPower factor = real power ÷ apparent power (DOE). The triangle’s third side, reactive power, is √(kVA² − kW²).
Worked examples
1,500 W heater on 120 VI = 1,500 ÷ 120 = 12.50 A · R = 120² ÷ 1,500 = 9.6 Ω
5 kW at 240 V, PF 0.855 × 1,000 ÷ (240 × 0.85) = 24.51 A (20.83 A at PF 1.0)
Power factor changes the answer. Heaters and incandescent lamps are resistive, PF 1.0. Motors and other inductive loads run lower, and their PF changes with load (DOE). Use the nameplate or a measurement; the calculator assumes no “typical” motor PF.
Three-phase means line-to-line voltage and a balanced load. For a line-to-neutral voltage or an unbalanced load the three-phase formulas do not apply as written.
kVA is not kW. kW = kVA × PF.
Current is not a wire or breaker size. Conductor and overcurrent sizing follow the electrical code and the equipment’s listing and instructions; this calculator does not apply them.
Sinusoidal loads. The relations hold for rms values of sine-wave voltage and current; results are not exact for nonlinear loads such as many electronic power supplies.