On this page8 sections

A customer wants a window unit for a converted garage. Another asks why your quote for a new system is a size smaller than the unit coming out. Both conversations end at the same question: how many BTU per square foot?

The answer depends on what you are sizing. For one room and one room air conditioner, there is a public federal chart you can use in a minute. For a whole house, the published guidance points to a load calculation, and the ratio stops being useful.

The ENERGY STAR chart: one room, one room unit

ENERGY STAR publishes a sizing chart on its Room Air Conditioners page. Measure the room in feet, converting inches to decimals (12 ft 6 in is 12.5 ft). Multiply length by width for a rectangle; for a triangle, multiply and divide by two; split odd shapes into rectangles and triangles and add them up. The page says the capacities assume an 8-foot ceiling.

Area to be cooled (sq ft)Capacity needed (BTU/h)
100 up to 1505,000
150 up to 2506,000
250 up to 3007,000
300 up to 3508,000
350 up to 4009,000
400 up to 45010,000
450 up to 55012,000
550 up to 70014,000
700 up to 1,00018,000
1,000 up to 1,20021,000
1,200 up to 1,40023,000
1,400 up to 1,50024,000
1,500 up to 2,00030,000
2,000 up to 2,50034,000

Source: ENERGY STAR, Room Air Conditioners, read October 4, 2026. The page shows no revision date.

The bands share their edge numbers, and ENERGY STAR doesn't say which row an exact 150 or 250 belongs to. Our BTU calculator puts an exact edge value in the smaller band (150 sq ft gives 5,000 BTU/h; 150.1 sq ft gives 6,000), because ENERGY STAR warns specifically against oversizing. That tie-break is our convention, not ENERGY STAR's.

The chart itself has no single BTU-per-square-foot figure

Divide each capacity by the floor area and the "per square foot" number falls, unevenly, as the room gets bigger:

Room area (sq ft)Chart capacity (BTU/h)BTU/h per sq ftSq ft per ton
1005,00050.0240
1505,00033.3360
2506,00024.0500
4009,00022.5533
70014,00020.0600
1,00018,00018.0667
1,50024,00016.0750
2,50034,00013.6882
Fig. 1 No single BTU per square footDrawn to scale: area in square feet
BTU/h per square foot from the ENERGY STAR room chart, area from 0 to 2,500 sq ft to scale. Within each band the figure falls as the room grows and jumps at the band edge: 100 sq ft 50.0, 150 sq ft 33.3, 250 sq ft 24.0, 400 sq ft 22.5, 700 sq ft 20.0, 1,000 sq ft 18.0, 1,500 sq ft 16.0, 2,500 sq ft 13.6.50.033.318.016.013.601020304050Room area, sq ftBTU/h per sq ft
Fig. 1 — BTU/h per square foot across the ENERGY STAR room chart. The figure falls inside each band and jumps at its edge, from 50.0 at 100 sq ft to 13.6 at 2,500 sq ft.

Within one federal chart, a 100 sq ft room gets about 3.7 times the BTU per square foot of a 2,500 sq ft open area (50.0 against 13.6). A calculator that multiplies square feet by one constant is not reproducing this chart, whatever it says about its source.

Back to contents

The four adjustments, and the order we apply them

ENERGY STAR lists four adjustments to the chart value:

  • Heavily shaded room: reduce capacity by 10%.
  • Very sunny room: increase capacity by 10%.
  • More than two people regularly in the room: add 600 BTU/h for each additional person.
  • Unit used in a kitchen: add 4,000 BTU/h.

ENERGY STAR doesn't say in what order to apply them. Our calculator applies the 10% to the chart value first, then adds people, then the kitchen. The order changes the answer: a 300 sq ft, very sunny kitchen comes out at 7,000 × 1.10 + 4,000 = 11,700 BTU/h our way, and 12,100 BTU/h if you add the kitchen before the 10%.

Three worked examples

  1. A 12 ft 6 in × 14 ft bedroom, normal sun, two people: 12.5 × 14 = 175 sq ft, which falls in the 150-to-250 band, so 6,000 BTU/h, or 0.50 tons.
  2. A 400 sq ft heavily shaded den used by four people. 400 is where two bands meet, so by the convention above it takes the smaller band, 9,000 BTU/h: 9,000 × 0.90 = 8,100, plus 2 × 600 = 1,200 for the two extra people, gives 9,300 BTU/h, or 0.78 tons.
  3. A 500 sq ft kitchen and dining area with three regular occupants: 12,000 + 600 + 4,000 = 16,600 BTU/h, or 1.38 tons.
Fig. 2 Example 2, drawnDrawn to scale: plan in feet, capacity in BTU/h
Room cooling estimate for the 400 sq ft shaded den, drawn to scaleFloor plan drawn as a square of the same area, about 20′-0″ a side, 400 square feet, in the ENERGY STAR band 350–400 square feet (9,000 BTU per hour). Capacity bar to scale: chart 9,000, sun or shade −900, people +1,200, kitchen none, total 9,300 BTU per hour.ARoom plandrawn as a square≈ 20′-0″≈ 20′-0″Floor area400 sq ft4 people051015ftBEnergy Star room chartsq ft → BTU/h100–1505,000150–2506,000250–3007,000300–3508,000350–4009,000400–45010,000450–55012,000550–70014,000700–1,00018,0001,000–1,20021,0001,200–1,40023,0001,400–1,50024,0001,500–2,00030,0002,000–2,50034,000CCooling capacityBTU/h, same scaleThis room132020,0009,300 BTU/h= 0.78 tons (÷ 12,000)
  1. ENERGY STAR chart350–400 sq ft band9,000
  2. Heavily shaded, −10%10% of the chart value−900
  3. People over two2 × 600+1,200
  4. Kitchennot a kitchen0
  5. Room estimate9,300 BTU/h
Fig. 2 — The 400 sq ft heavily shaded den used by four people. The chart gives 9,000 BTU/h; minus 10% for shade and plus 600 for each of the two extra people, the estimate is 9,300 BTU/h, 0.78 tons.

For ceilings above 8 feet, ENERGY STAR says you may want a larger unit but gives no factor. Our tool doesn't invent one, and a quote shouldn't either. Rooms under 100 sq ft or open areas over 2,500 sq ft are off the chart; the tool shows no number for them.

Converting to tons and kilowatts

A ton of refrigeration is defined as 12,000 Btu per hour (NIST Guide to the SI, Appendix B.9). So tons = BTU/h ÷ 12,000: the 9,300 BTU/h den above is 0.775 tons, and the chart's top value of 34,000 BTU/h is 2.83 tons. For kilowatts, multiply BTU/h by NIST's factor of 0.2930711 and divide by 1,000; 12,000 BTU/h is 3.517 kW.

Converting units doesn't make a number more accurate. A tonnage figure from a room chart is still a room estimate, and matching a load to a nominal equipment size is the installer's call, using the manufacturer's data.

Why square-foot rules oversize whole houses

The Department of Energy's Building Science Education Solution Center says rules of thumb are too often used to size comfort systems and produce excessively oversized equipment: higher cost, wasted energy, and too-frequent on-off cycling that can compromise comfort and efficiency (DOE). ENERGY STAR says the same about central equipment: bigger is not always better, and a conventional system that's too large may short-cycle, causing humidity control problems and inefficient operation (ENERGY STAR). For room units, ENERGY STAR adds that an oversized unit cools the room before it removes the humidity, leaving it damp and clammy.

An older ENERGY STAR sheet on heating equipment is more direct still: load calculations from ACCA Manuals J and S are more accurate than rule-of-thumb estimating, and it names square-footage ratios as the example (ENERGY STAR, PDF).

Look at what the room chart already needs to get one room right: four adjustments and an assumed ceiling height. A house is many rooms with different exposures and uses, and the published guidance sends that job to a load calculation rather than to a bigger ratio.

Manual J: what it is and where codes come in

ACCA describes Manual J 8th Edition (ANSI/ACCA 2 Manual J – 2016) as the national ANSI-recognized standard for producing equipment sizing loads for single-family detached homes, small multi-unit buildings, condominiums, townhouses and manufactured homes. ACCA also states that a load calculation done to Manual J is required by national building codes and most state and local jurisdictions (ACCA). ACCA sells Manual J; we describe it here and don't reproduce it.

ENERGY STAR tells homeowners to make sure their contractor verifies the system size with Manual J and follows ACCA Manuals J and S and Standard 5. DOE adds that equipment, including ducts, should be selected from those loads and that the blower must deliver the airflow the loads call for. On the duct side, our duct size calculator checks one round duct section by the equal-friction method (see duct sizing by friction rate); it is not a Manual D design.

Whether a load calculation must go in with the permit, and which code edition applies, depends on where you work. This is general information, not code advice: ask your local building department. The model residential code can be read on ICC Digital Codes.

Heating is a separate question. Our calculator doesn't estimate it: we found no federal or code-body source that gives a square-foot heating method, and ENERGY STAR's heating guidance points to Manual J.

What to tell the customer

  • Window, through-the-wall or similar single-room unit: use the chart and the four adjustments. That is the job ENERGY STAR built it for.
  • Central air conditioner or heat pump: the size comes from a load calculation of the house, not from its square footage. ENERGY STAR tells homeowners to expect their contractor to do exactly that, so saying so on the estimate is not an upsell.
  • A replacement where the refrigerant question is also on the table: sizing and refrigerant rules interact; see R-410A after the 2026 EPA rule.

Back to contents

Next step

Run a room through the BTU calculator. It applies the ENERGY STAR chart, the four adjustments in the order described above, and converts the result to tons and kilowatts. For anything bigger than one room or one open area, treat the number as a sanity check and size the equipment from a Manual J load calculation.

Sources

  1. Room Air ConditionersENERGY STAR (U.S. EPA and DOE)
  2. Clean Heating and CoolingENERGY STAR (U.S. EPA and DOE)
  3. ENERGY STAR Qualified Heating Equipment (PDF)ENERGY STAR (U.S. EPA and DOE)
  4. HVAC Proper Sizing of HVAC SystemsU.S. Department of Energy, Building Science Education Solution Center
  5. Manual J Residential Load CalculationAir Conditioning Contractors of America
  6. NIST Guide to the SI, Appendix B.9: Factors for units listed by kind of quantity or field of scienceNational Institute of Standards and Technology

Tools for the job

Tool listHVAC + Cross-trade4 itemsSpecs read

As an Amazon Associate, Trade Price Book earns from qualifying purchases. Amazon links are marked “(paid link)”; prices aren’t shown here.

  1. Digital manifolds and probesFieldpiece JL3KH6

    JL3KH6 Job Link System Probes Wireless Charge & Air Test Kit

    • Six probes in a padded case: 2 pressure probes, 2 pipe-clamp temperature probes and 2 psychrometers.

    Specs: Fieldpiece product page, read

    View on Amazon for Fieldpiece JL3KH6(paid link)

  2. Airflow and static pressureFieldpiece STA2

    STA2 In-Duct Hot Wire Anemometer

    • Air velocity 40 to 3,960 fpm at 1 fpm resolution; accuracy ±(5% + 1 digit) of reading or ±(1% + 1 digit) of full scale.

    Specs: Fieldpiece product page, read

    View on Amazon for Fieldpiece STA2(paid link)

  3. Thermal imagersFluke TiS20+ MAX

    TiS20+ MAX Thermal Imaging Camera

    • 120 x 90 (10,800-pixel) infrared resolution, 60 mK thermal sensitivity, 9 Hz.

    Specs: Fluke product page, read

    View on Amazon for Fluke TiS20+ MAX(paid link)

  4. Laser distance metersBosch GLM400CL

    BLAZE Outdoor 400 Ft. Connected Lithium-Ion Laser Measure with Camera

    • Range up to 400 ft with accuracy up to ±1/16 in.

    Specs: Bosch product page, read

    View on Amazon for Bosch GLM400CL(paid link)

How tools are chosen for gear listsAll 20 HVAC tools

Newsletter

Get an e-mail when Trade Price Book publishes something new

At most one e-mail a day, only about new guides and tools. No tracking pixels. How we handle your address