A recirculation loop can look like a pump-sizing job, but the pump only has to replace the heat the pipes lose. In the example below that is under half a gallon per minute, and the pipes and stubs decide whether the system works.
This guide shows the arithmetic in the order a designer or a shop doing a retrofit would use it: heat loss, then flow, then the stub to each fixture, then pipe size. It describes what the sources say and is not a design for any particular building.
What a loop actually does
A loop pulls water through a supply line that runs close to the fixtures and sends the cooled water back to the heater. The Building America Solution Center puts the loop ideally within 10 feet of every fixture and describes the pump as drawing hot water through the supply side while returning water that has cooled to the heater.
That page adds that in a 1,200-square-foot house with a trunk-and-branch layout the volume to the farthest fixture can pass 1.5 gallons, with a time to the tap of more than 90 seconds. The loop exists to cut that wait.
Pumps run continuously, on a timer, or on demand (a button or sensor). The same Solution Center page says demand-initiated systems were found to be more energy efficient than timer or temperature-based ones, because hot water is drawn into the loop only when it is wanted. EPA's WaterSense fact sheet says the same about demand activation, and the Department of Energy's Zero Energy Ready Home specification for multifamily buildings requires on-demand recirculation that works from a demand indicator and the loop water temperature (as presented in its April 2017 webinar slides).
Step 1: heat loss sets the flow
The pump has to supply enough hot water to replace what the supply piping gives up to the air. The manufacturer publication from Caleffi gives the formula:
Flow (gpm) = heat loss (Btu/h) ÷ (500 × allowed temperature drop in °F)
The 500 is the same rounded constant used in the tankless guide and derived in the water heater sizing guide: about 8.34 pounds per gallon times 60 minutes. For the heat loss, Caleffi's example assumes 1/2-inch elastomeric foam insulation on copper, water averaging 135 °F and room air at 70 °F. At those conditions it lists these losses per foot of supply pipe (as of its October 2022 article):
| Insulated copper, nominal | Heat loss, Btu/h per ft |
|---|---|
| 3/4 inch | 9.5 |
| 1 inch | 11.2 |
| 1-1/4 inch | 12.9 |
Caleffi lists them for insulated copper tubing without naming a type; we apply them to Type L as an example. They change with water temperature, air temperature, insulation and pipe, so they are an example of the method, not a table for your job. Caleffi's formula counts the supply piping; the return line carries the cooled water back and is not part of its heat-loss total.
Worked example
Take a loop with 120 feet of 3/4-inch Type L supply and 80 feet of 1-inch Type L supply, insulated and at the conditions above. These lengths are an example, not typical values.
- 3/4-inch: 120 ft × 9.5 = 1,140 Btu/h
- 1-inch: 80 ft × 11.2 = 896 Btu/h
- Total: 2,036 Btu/h
At a 10 °F allowed drop: 2,036 ÷ (500 × 10) = 0.41 gpm. The drop you allow matters a lot, because halving it doubles the flow:
| Allowed drop | Pump flow, gpm | Minutes for the water to make one trip around the loop |
|---|---|---|
| 5 °F | 0.81 | 7.9 |
| 10 °F | 0.41 | 15.8 |
| 15 °F | 0.27 | 23.7 |
| 20 °F | 0.20 | 31.7 |
The trip time uses the loop volume from the gallons-in-a-pipe tables: 3.02 gallons in the 3/4-inch run plus 3.43 gallons in the 1-inch run is 6.45 gallons. You can check any run with the pipe volume calculator.
Caleffi points out that this flow only satisfies the heat balance for the whole supply piping. It does not guarantee the farthest fixture stays within 10 °F of the heater, and a multi-branch system needs balancing so each branch gets enough flow.
Step 2: check velocity and head, which come out small
At 0.41 gpm the velocities are low. Using the site's velocity formula, 0.41 gpm runs about 0.27 ft/s in 3/4-inch Type L, 0.16 ft/s in 1-inch and 0.56 ft/s in a 1/2-inch return. The copper erosion limits of 5 and 8 ft/s covered in that guide are not close to being a concern here.
Friction is small too. With Hazen-Williams at C = 150 (a site default), 0.41 gpm through the supply runs above and a 200-foot return of 1/2-inch Type L (a length assumed for the example) loses about 0.35 psi, or 0.81 feet of head, and most of it is in the narrow return. The 1/2-inch return is Caleffi's size; the Solution Center minimum discussed below is 3/4-inch, which would cut the return loss to about 0.05 psi. Hazen-Williams was built for turbulent flow, so treat friction at this low velocity as rough. That is pipe only. Fittings, check valves, balancing valves and any heat-trap or thermostatic hardware add to it, so use the manufacturer's pump curve and instructions for the real selection. The flow and velocity calculator does the pipe part.
Step 3: the stub decides the wait
A loop does not put hot water at the faucet. It puts it at the tee where the stub to the fixture leaves the loop. The customer still waits for the water standing in that stub. EPA's WaterSense fact sheet, in an optional measure for WaterSense Labeled Homes, calls 0.5 gallons or less between the water heater and each end use "a good target." It suggests checking by running the farthest fixture into a bucket until the water warms 10 °F and measuring the volume collected. The Department of Energy's multifamily slides (Rev. 06 of its specification; later revisions may differ) list a stored volume of 1.0 gallon or less between the loop and the furthest fixture as encouraged, not required.
A loop's stub starts at the loop tee, so the stub volume is what counts. The gallons-in-a-pipe guide has the length that holds 0.5 gallons for each pipe and the code limit on developed length. For instance, 20 feet of 1/2-inch Type L holds 0.24 gallons and empties in about 10 seconds at a 1.5 gpm lavatory flow, while 20 feet of 3/4-inch holds 0.50 gallons. Keeping the loop within 10 feet of every fixture, as the Solution Center advises, means a short stub in a small pipe, which holds little water.
Step 4: pipe size and insulation
The sources do not agree on one loop size, which is a reason to follow the design or specification the job is built to. The Solution Center guide says the supply and return portions of the loop shall be no smaller than 3/4-inch nominal. Caleffi's worked example uses a 1/2-inch copper return. The code body, the specification the project follows and the local code official decide what applies where you work; the model plumbing codes are free to read online through ICC Digital Codes and IAPMO.
Insulation does the other half of the work, because every Btu/h saved is flow you do not need. EPA's fact sheet says to use pipe insulation with a minimum R-value of R-3. The DOE multifamily slides list R-4 pipe insulation as encouraged, and also recommend a pump setting at least 5 °F below the water heater setpoint. The Solution Center notes that the 2015 IECC (an older edition; adopted editions differ) calls for insulation on all piping 3/4-inch nominal and larger. Whether any of this is a requirement on your job depends on the code your state or city has adopted.
Pump controls matter too. The Solution Center says controls should stop the pump when the right temperature change is measured and should not run it if the water is above 105 °F, and the DOE slides describe demand control as turning the pump on and off automatically from building demand and water temperature. Follow the manufacturer's installation manual for the control you are installing.
Bottom line
Heat loss sets the loop flow, the stub sets the wait, and the pipe sizes follow from the specification you are working to. Before you promise a customer a result, work the numbers in this order:
- List the supply footage by pipe size and get the heat loss per foot from the insulation and pipe manufacturer.
- Divide the total Btu/h by 500 times the allowed drop to get gpm, then add the pipe friction and the valves to pick a pump from its curve.
- Measure each stub's volume with the pipe volume calculator and compare it with the 0.5-gallon WaterSense target.
Hot water systems also involve scald and water-quality questions, and code or health rules can apply to temperatures and controls. This guide is general information, not design or code advice; check with the local building department or authority having jurisdiction before you design or install a loop.